Technical Specifications for 1756-irt8i

ManufacturerAllen-Bradley / Rockwell Automation
SeriesControlLogix
Part number1756-IRT8I
Product typeI/O module
Module typeRTD/thermocouple input module
Inputs8
Input current at 5.1 Volts DC200 milliamps
Input current at 24 Volts DC150 milliamps
Peak overvoltage protection+/-30 Volts DC
Normal mode noise rejection75 dB at 60 Hertz
RTD excitation current600 microamps
Operating temperature32 to 140 degrees Fahrenheit
EnclosureOpen

Manufactured by Allen-Bradley/Rockwell Automation, the 1756-IRT8I is a high-resolution analog I/O module. Specifically, it is an 8-point isolated combined temperature and millivolts-sensing input module. The 1756-IRT8I module is a member of the ControlLogix system, and it requires a 36-pin RTB, or a detachable terminal block housing. This can be either the 1756-TBS6H or the 1756-TBCH. The Allen-Bradley 1756-IRT8I has 8 isolated channels for use in any combination of RTD or Thermocouple modes. The Allen-Bradley 1756-IRT8I ControlLogix RTD Thermocouple Input Module is equipped with 2 CJC sensors for thermocouple use, but they can be ordered separately. The accuracy of local CJC sensor is +/- 0.3 degrees Celsius, and this is the same as remote CJC sensor accuracy. The 1756-IRT8I module’s channel sampling rate is determined only by the RPI value since the 1756-IRT8I does not offer RTS parameter. Similarly, channels configured for the thermocouple inputs does lead resistance self-calibration if the module power is cycled.

Some of the properties of the 1756-IRT8I module are the notch filter, multiple module input ranges, digital filter, rate alarm, under-range/over-range detection, 10-ohm copper offset, process alarms, sensor offset, sensor types, wire off detection, synchronized sampling, temperature units, thermocouple wire length compensation, and the cold junction compensation. The 1756-IRT8I ControlLogix RTD Thermocouple Input Module features improved analog I/O modules, three 8-channel isolated designs as well as 12 and 16-channel non-isolated designs all with the enhanced functionality of the analog I/O. This module provides faster performance, is more accurate, and presents better resolution and cost savings than other analog I/O modules because there is less space needed in its chassis for extra modules and power supplies.

The Allen-Bradley 1756-IRT8I module is an RTD/thermocouple analog input module. There are 8 isolated input channels on the module. The module can support any combination of thermocouple or RTD inputs. Two CIC (catalog number 1756-CIC) sensors are required for thermocouple use and they need to be ordered separately. The recommended non-operating temperature range is from -40 to 185 degrees Fahrenheit. The recommended operating temperature range is from 32 to 140 degrees Fahrenheit. The 1756-IRT8I module is approved by the KC, EAC, IECEx, CE, and RCM standards. Category 2 wire is recommended for the signal ports. The wire size recommended by Allen-Bradley is 22 to 14 AWG solid or stranded copper wire. The 1756-IRT8I module is compatible with the 1756-TBCH and 1756-TBS6H removable terminal blocks.

The configurable input ranges on the 1756-IRT8I module are -100 to 100 millivolts, 8 to 4000 Ohms, 4 to 2000 Ohms, 2 to 1000 Ohms, and 1 to 500 Ohms. The 1756-IRT8I module supports 24-bit resolution. RTD sensors supported by the 1756-IRT8I module include platinum (alpha = 385), copper (alpha = 427), nickel (alpha = 672), and nickel (alpha = 618). Multiple thermocouple types are supported, including the B, C, D and K type. The current drawn by the 1756-IRT8I module at 24 Volts DC is 150 milliamps, and at 5.1 Volts DC, it is 200 milliamps. The RTD excitation current is 600 microamps and the input impedance is 1 gigaohm. The peak overvoltage protection rating is +/-30 Volts DC. The normal mode noise rejection at 60 Hertz is 75 dB. The channel bandwidth on the module is dependent on the notch filter configuration.
The ControlLogix 1756-IRT8I module is a combination I/O module. The input channels on the module can be used as RTD inputs or thermocouple inputs.

F.A.Q for 1756-irt8i

All online orders placed before 4:30 PM EST “SHIPS SAME DAY FREE!" World’s largest warehouse of Factory Sealed GE 90-30 PLC, GENIUS I/O and RX7i PACSystem.highlight_off

PDF Electric & Supply Inc. sells new, new surplus and refurbished products which are sourced through independent channels. All warranties and support, if applicable, are with PDF Electric & Supply Inc. and not the manufacturer. PDF Electric & Supply Inc. is not an authorized distributor or representative for the listed manufacturers and makes no representations as to any quality control performed by any listed manufacturer on the products. The products listed on this website may vary as to their country of origin; the accessories, and other items included with the product; and the language used on the packaging, the parts, and any related instructions or printed material related to the products. This website is not sanctioned or approved by any manufacturer or tradename listed. Designated trademarks, brand names and brands appearing herein are the property of their respective owners.