GE / IP FANUC Series 90/30 In Stock

Call Now

1-800-360-6802

Mon-Fri 8AM-5PM EST

1-919-535-3180

IC660BBA103

Rated 4.7/5 Based on 23 ratings.

Rate your purchase of the IC660BBA103

IC693PWR324 IC660BBA103 In Stock! Block 115Vac/125Vdc Thermocouple Input 6 Channels IC660B IC660BB IC660BBA PDFs IC660BBA103 In Stock! Block 115Vac/125Vdc Thermocouple Input 6 Channels IC660B IC660BB IC660BBA PDFs IC660BBA103

SKU 2175428  UPC 0799705793514

Lowest Price Guarantee

Order Today - Ships Today!

*US continental orders placed Monday-Friday before 4:30pm EST!

MSRP $6396

New

$3950

(Save 38%)

4 In Stock

2 Year warranty

*Need a Specific Revision?

New Surplus

$2550

(Save 60%)

3 In Stock

3 Year warranty

*What is New Surplus?

Reman

$795

(Save 87%)

24 In Stock

2 Year warranty

*What is Remanufactured?

Repair Service

$595

(Save 90%)

Fast or Free!

2 Year warranty

*What is Fast Repair?

Other Available Revisions for the IC660BBA103 ABCCADEFHKLMNPQRRRSTTCC1

Product Description



The IC660BBA103 is a Thermocouple Block of series 90-30 of GE Fanuc PLCs.
It has two isolated equal groups of six thermocouple inputs. It can be powered with either 115 VDC or 125 VAC power. It has a capability of working with 24 or 48 VDC since it comes in two versions. The temperature input signal is measured per 10μV, but in certain conditions, accuracy can drop up to 20μV. The block deploys six thermocouple types, each having dissimilar temperature range and accuracy. Temperature range is between the absolute zero and several thousands of Celsius degrees. The measurements can display in Volts, Celsius, or Fahrenheit.

The IC660BBA103 Thermocouple Block has 32 terminals. Input power, bus switching module control, and field wiring devices can connect to inputs 5 to 32 with AWG #22 or #14 wires. Input block power connects to terminals 5 and 6, and bus switching module connects to terminals 7 and 8. There are also six channels where thermocouple wires connect and two remote cold junction connection inputs.

This equipment can provide the system with a wide range of diagnostics. These include internal fault of open wire error in the block, indication that a one of the thermocouples has exceeded its range, and two types of alarms set by the user. Every input can be set to start a high or low alarm. If the alarm is triggered, circuit faults must be cleared.

To present an accurate temperature measurement, the IC660BBA103 thermocouple block combines temperature measurements. Those come from thermocouple volt signals and cold junction compensation.  After power is isolated from each input, an optical coupler provides accurate signal isolation. The volt current frequency signal continues to measure the signal during 400ms. During this time, a multiplexer processes cold junction measurements and internal references. This helps to further decrease the chance of error. Cold junction measurements can apply remotely.

The user can calibrate internal references. If there is a difference between the cold junction temperature and the output measurement, it is possible to set an offset. Using a handheld monitor, the operator can use different compensation methods, disable or enable inputs, and set alarms.


Technical Specifications


Rated Voltage: 115 VAC/ 125 VDC
# of Points: 6
Input Interface: J, K, T, E, B, R, S and N thermocouples 
Input measurement: Adjusted up to +/-100 deg C or F
Operating Voltage: 93-132 VAC / 105-145 VDC
Points per Common:  3 groups of 2

 

Technical Information

Specifications  

Block Type:

Six thermocouple–compatible inputs, three isolated groups of two.

CatalogNumbers:

115 VAC / 125VDCThermocoupleBlock TerminalAssemblyOnly

Electronics Assembly Only

24 / 48 VDC ThermocoupleBlock TerminalAssemblyOnly Electronics Assembly Only

 

IC660BBA103 IC660TBA103 IC660EBA103

IC660BBA023 IC660TBA023 IC660EBA023

Size (Height x width x depth):

Weight:

LEDs (I/O Block): HeatDissipation:

8.83” (22.44cm) x 3.50” (8.89cm) x 3.94” (10.00cm)

4 lbs. (1.8 kg)

UnitOK,I / OEnabled 9Wmaximum

Block to Block Isolation: Group to GroupIsolation:

1500 V for one minute 300 V

115VAC/125 VDCblockpower:

Powersupplyvoltage

Power supply dropout time:

115 VAC 125 VDC

93–132  VAC @ 9W 105–145 VDC  @ 9W

47–63 Hz 10% max. ripple

1 cycle 10 mS

24/48 VDCblockpower:

Powersupplyvoltage Power supply dropout time

 

18–56 VDC @ 9W, 10% max. ripple 10mSminimum

InputCharacteristics:

Voltagemeasurement: Range

Resolution Accuracy  (at 25C)

Bandwidth of input amplifier filter Temperaturecoefficient

 

–25.0mV  to +150mV

Less than $ 4 V

Less than $ 10V error typ, 20Vmax. 8 Hz

$ 2V / C typical

Internal Cold Junction Measurement:

Range

Offset at 25C Linearity Resolution

Temperaturecoefficient

 

0  to 60C

2 C typ. User adjustable to zero at any temperature.

$ 0.15C

Less than $ 0.01C

$    0.05    per C

External Cold Junction Measurement:

Range

Scalefactors Resolution Accuracy

 

–25.0C   to   +150.0  C

1.0C per millivolt, 1.0K per microampere Less than 0.01  C

$ 0.1C

Input update time (all channels):

2.0 sec (typ), 3.0 sec (max)

Openwire detection response:

less than 5.0 seconds

Diagnostics:

Open Wire, Overrange, Underrange, High Alarm, Low Alarm, Internal Fault

Environmental:

Operating Temperature Storage Temperature Humidity

Vibration:

 

0C   to   +60C   (+32F   to  +140F)

–40C to +100 C   (–40F   to  +212F)

5% to 95% (non–condensing)

5–10 Hz 0.2” (5.08mm) displacement, 10–200 Hz at 1G

 

Troubleshooting

Troubleshooting IC660BBA103

Troubleshooting information is available on IC660BBA103's website page; it also includes a datasheet, a user manual, and a wiring diagram.


Repair your IC660BBA103

PDF Supply can repair your IC660BBA103 in 3-5 business days. And PDF Supply stands by all of its repairs with a 1 year customer satisfaction warranty.

 

Customer Questions and Answers


  • Question:  What is an IC660BBA103?  Answer:  The IC660BBA103 is an 115 VAC/125 VDC Thermocouple Input Block from the GE Fanuc Genius I/O Series. This block is primarily used for monitoring temperature with standard thermocouple types connected to the inputs. It can also be used for measuring low-level voltage input signals.
  • Question:  What is the difference between IC660BBA103 and IC660BBA023?  Answer:  The only difference between these blocks is their power supply.
  • Question:  How many input circuits does IC660BBA103 have?  Answer:  This block has 6 input circuits. (They are in 3 separate groups.)
  • Question:  How much common mode voltage is allowed between 2 points in one group?  Answer:  +/- 10 V
  • Question:  What does each group have?  Answer:  Each group has 2 thermocouple input circuits and 2 remote cold junction compensation inputs.
  • Question:  What is the group to group isolation?  Answer:  300 volts
  • Question:  The configuration of each channel can be to use what?  Answer:  The configuration of each channel on IC660BBA103 can be to use an internal sensor, an external sensor, or an user-defined value for cold-junction compensation.
  • Question:  What diagnostic tests does IC660BBA103 perform?  Answer:
    • Internal fault detection
    • Open Wire detection
    • Over range and under range input indication
    • High and low input alarms
  • Question:  What should I do if my IC660BBA103 has failed?  Answer:  Your IC660BBA103 may need repair

For more information on the IC660BBA103 Thermocouple Input Block of the GE Fanuc Genius I/O Series, please see the Datasheet User-Manual.

The final letter in the part number (ex. IC660BBA103K) indicates the revision. Revision K and later use the newer style electronic housing and therefore need the newer style plastic door and may indicate some compatibility issues with the terminal strip.

Common related search terms: ConfigurationDatasheetManualPDFPLCPriceRepairSpecificationTroubleshootUser-ManualWiring

PDF Electric & Supply Inc. sells new, new surplus and refurbished products which are sourced through independent channels. All warranties and support, if applicable, are with PDF Electric & Supply Inc. and not the manufacturer. PDF Electric & Supply Inc. is not an authorized distributor or representative for the listed manufacturers and makes no representations as to any quality control performed by any listed manufacturer on the products. The products listed on this website may vary as to their country of origin; the accessories, and other items included with the product; and the language used on the packaging, the parts, and any related instructions or printed material related to the products. This website is not sanctioned or approved by any manufacturer or tradename listed. Designated trademarks, brand names and brands appearing herein are the property of their respective owners.

TOP