GE / IP FANUC Series 90/30 In Stock
The GE Fanuc IC693MDL260 is a 120VAC Grouped Input module. It provides 32 discrete input points, which are arranged in four separate groups of eight points each. Between each group, isolation is provided. However, all inputs share a single common connection.
When the MDL260 is installed in a 90-30 PLC system, the user can control the input filter times by operating the DIP switch. This switch is on the back of the module.
Rated Voltage: | 120 volt AC |
# of Inputs: | 32 |
Freq: | 50/60 Hz |
Input Current: | 12 mA at rated voltage |
Input Voltage Range: | 0 - 132 volts AC |
DC Power: | No |
Rated Voltage |
120 volts AC |
Input Voltage Range |
0 to 132 VAC (47 to 63Hz) |
Inputs per Module |
32 (four isolated groups of 8 inputs) |
Isolation, Field to Backplane |
264VAC continuous; 1500 VAC for one minute |
(optical) |
|
Isolation, Group to Group |
264VAC continuous; 1500 VAC for one minute |
Thermal Derating |
See next page |
Input Current |
7.0 mA per point (typical) at rated voltage |
Input Filter Times |
20ms to 2540ms in 20ms increments. Sent from CPU. Enabled by DIP switch. |
Power Consumption |
220mA at 5VDC with all inputs on |
Diagnostics |
Terminal block presence reported to RX3i CPU only |
Input Characteristics |
|
On–state Voltage |
70 to 132 VAC |
Off–state Voltage |
0 to 20 VAC |
On–state Current |
5mA minimum |
Off–state Current |
2.5mA maximum |
On/Off response Time |
+0-1 AC cycles for filter times up to 840ms, +1-2 AC cycles for filter times of |
|
840 to 1600ms, +2-3 AC cycles for filter times of 1600 to 1920ms, +3-4 AC |
|
cycles for filter times of 1920ms or more |
Troubleshooting IC693MDL260
Troubleshooting information is available on IC693MDL260’s website page; it also includes a datasheet user-manual and a wiring diagram.
Repair your IC693MDL260
PDF Supply can repair your IC693MDL260 in 3-5 business days. And PDF Supply stands by all of its repairs with a 1 year customer satisfaction warranty.
IC693MDL260 System Configuration Mismatch
Description
Issues with the IC693MDL260 or IC694MDL260 modules, such as system configuration mismatch errors, or the inability to read the inputs, are often caused by the DIP switch settings on the back of the module.
Resolution
The DIP switch settings must match the software configuration settings for the Hardware. If Input Filters are enabled, move both DIP switches to the right. Some manuals may show that the bottom switch is Not Used; however, it may need to be put to the right to avoid issues.
For more information on the IC693MDL260 Grouped Input Module of the GE 90-30 Series, please see the Datasheet Manual.
Release |
Comments |
IC694MDL260-AA IC693MDL260-AA |
Initial Release |
Common related search terms: Buy, Datasheet, Emerson, Manual, Price, Repair, Specification, Troubleshoot, Wiring,
PDF Electric & Supply Inc. sells new, new surplus and refurbished products which are sourced through independent channels. All warranties and support, if applicable, are with PDF Electric & Supply Inc. and not the manufacturer. PDF Electric & Supply Inc. is not an authorized distributor or representative for the listed manufacturers and makes no representations as to any quality control performed by any listed manufacturer on the products. The products listed on this website may vary as to their country of origin; the accessories, and other items included with the product; and the language used on the packaging, the parts, and any related instructions or printed material related to the products. This website is not sanctioned or approved by any manufacturer or tradename listed. Designated trademarks, brand names and brands appearing herein are the property of their respective owners.