GE / IP FANUC Series 90/30 In Stock

Call Now

1-800-360-6802

Mon-Fri 8AM-5PM EST

1-919-535-3180

IC693PCM301

Rated 4.6/5 Based on 15 ratings.

Rate your purchase of the IC693PCM301

IC693PWR324 IC693PCM301 In Stock! IC693PCM PCM 192 KB IC693P IC693PC IC693PCM PDFsupply also repairs GE IP FANUC IC693PCM301 In Stock! IC693PCM PCM 192 KB IC693P IC693PC IC693PCM PDFsupply also repairs GE IP FANUC IC693PCM301

SKU 2176059  UPC 0313542047595

Lowest Price Guarantee

Order Today - Ships Today!

*US continental orders placed Monday-Friday before 4:30pm EST!

MSRP $4250

New

$2750

(Save 35%)

3 In Stock

2 Year warranty

*Need a Specific Revision?

New Surplus

$1550

(Save 63%)

1 In Stock

3 Year warranty

*What is New Surplus?

Reman

$695

(Save 83%)

10 In Stock

2 Year warranty

*What is Remanufactured?

Repair Service

$497

(Save 88%)

Fast or Free!

2 Year warranty

*What is Fast Repair?

Other Available Revisions for the IC693PCM301 ABCCADEFGHJKLLTMNPQRRRS

Product Information

 

General: The IC693PCM301 is a Programmable Coprocessor Module (PCM) manufactured by GE Fanuc Automation North America, Inc.  It is a high-functioning microcomputer that is compatible with the Series 90-30 Modular CPUs (Programmable Logic Controller system). The programming languages supported by the IC693PCM301 include Modbus RTU, GE Fanuc CCM protocols, MegaBasic and C. This version of the PCM has a total memory of 192K and a user MegaBasic memory of 47K.  

Any CPU baseplate slot can host a IC693PCM301 with the exception of the CPU module's slot 1. Furthermore, a PCM doesn't function within the Expansion, Remote racks, or the Embedded CPU (CPU311, 313, or 323) rack.

Specific: The IC693PCM301 can be programmed to operate as a one or two independent CCM ports, a CCM port, and a MegaBasic application using one serial port or a MegaBasic application using one or both serial ports. These modules are used for communicating with programming terminals, CRTs, bar code readers, scales, printers, ASCII devices, RTU master devices, etc.

Ports: The two ports available on the IC693PCM301 are accessed by a common connector at the front of the model.  IC693CBL305 Wye cables split out the two PCM port connections from the single connector on the faceplate. The module has three LED indicator lights. While one flashes to convey the condition of the module, the other two LED lights function to indicate activity in the respective ports. The latter group of indicators are subject to configuration by the user.

Restart Pusbutton: The restart pushbutton of the IC693PCM301 allows the user to change the mode of the module between "Run" and "Program". IC690CBL701/702/705 cables provide a direct RS-232 connection between the PCM and various programmers’ serial ports. These cables are not supplied with the PCM modules.

Memory: The RAM memory backup is handled by a lithium battery that is mounted on the inner side of the module's faceplate. It requires connection prior to instalment. The battery is to remain connected as long as the program in RAM memory is to be stored. It is advisable to disconnect and remove the battery during long term storage.

Technical Specifications

 

PCM

Programmable Coprocessor Module

Supports

Modbus RTU and GE Fanuc CCM

Memory Backup

Lithium Battery provided

Replacement Battery

IC693ACC301 (pkg of 2)

Battery Backed RAM

192 K or EPROM option

Internal Power

425 mA @ 5 VDC

 

Need more help?

Email us at sales@pdfsupply.com

You can order the GE Fanuc IC693PCM301 directly from our website.  

All orders placed Monday - Friday before 3:30pm EST will be shipped same day.

Free UPS Ground Shipping!  

We also offer repair services for the GE Fanuc IC693PCM301.

Email us at sales@pdfsupply.com or Request a Formal Quote for IC693PCM301.

Technical Information

 

PCM

Programmable Coprocessor Module

Supports

Modbus RTU and GE Fanuc CCM

Memory Backup

Lithium Battery provided

Replacement Battery

IC693ACC301 (pkg of 2)

Battery Backed RAM

192 K or EPROM option

Internal Power

425 mA @ 5 VDC

 

Need more help?

Email us at sales@pdfsuply.com or Request a Formal Quote for IC693PCM301.

All orders placed Monday - Friday before 3:30pm EST will be shipped same day.

Free UPS Ground Shipping!  

Troubleshooting

Troubleshooting IC693PCM301

Troubleshooting information is available on IC693PCM301's website page; it also includes a datasheet user-manual and a wiring diagram.  

 

Repair your IC693PCM301

PDF Supply can repair your IC693PCM301 in 3-5 business days. And PDF Supply stands by all of its repairs with a 1 year customer satisfaction warranty.

To Format and Write To PCM301 EPROM Megabasic

Description

Using the EPROM in a PCM must be formatted in Megabasic.

Resolution

J (Format EEROM device)

Format: J ROM

This command causes an electrically erasable ROM (EEROM) device installed in a PCM 301 to be erased and formatted as the file device ROM:. Once the EEROM has been formatted, files can be loaded to and run from it just as they are in RAM:. Note that only the PCM 301, IC693PCM301, supports an optional EEROM device. Attempting to format an invalid device produces this message: Unknown device

Save rom: MyProg.pgm

Saves the program to the EEROM.

 

PLC90/30 Debugging a PCM Task Using TERMF Software

Description

Debugging a PCM Task using TERMF Software

Resolution

PCM Support Software (TERMF), revision 1.00 or later, is required for terminal emulation and file transfer between the PC and PCM. (Series 90-30 PCM model IC693PCM300, IC693PCM301, IC693PCM311)

PCM firmware version 3.00 does not include a runtime debugger. The best debug method currently available is to use printf statements to trace program execution and display program data. Applications which use both PCM serial ports for communication can log execution trace data to a PCM file or named memory module.

Series 90-70 PCM applications can log trace data to a reserved memory block in VME dual port memory. A second PCM can be used to read the data in VME master mode. When an application task locks up, the PCM task state dump facility can be used to diagnose the cause. For more information on this topic, see "Dumping PCM task state information" in GFK-0771A chapter 7, Multitasking.

Some developers of PCM C applications use hardware debuggers. See "Debugging Multiple Tasks" in chapter 7, Multitasking, for more information on hardware debuggers.

 

PLC90-30 Running a PCM Task Using TERMF Software

PCM Support Software (TERMF), revision 1.00 or later, is required for terminal emulation and file transfer between the PC and PCM. (Series 90-30 PCM model IC693PCM300, IC693PCM301, IC693PCM311)

The PCM R (Run) command is used to execute an .EXE file as a PCM task.

At the PCM prompt, type: R HELLO.EXE.

The file extension ".EXE" is required by the PCM command interpreter. When the program is executed, TERMF will display its output:

Hello, world!

Running as task of hex under VTOS version 3.00.

The Run command can also be used to load PCM programs from your PC. If the specified .EXE file has not been stored to the PCM, the command interpreter will ask TERMF to look in the current PC directory. If the file is found there, it will be loaded and then run.

 

Customer Questions and Answers


  • Question:  What is an IC693PCM301?  Answer:  The IC693PCM301 is a Programmable Coprocessor module from the GE Fanuc Series 90-30. This module is a high performance microcomputer designed to perform coprocessor functions in a Series 90 PLC system. It combines the function of the Communications Module (CCM) and the ASCII/BASIC Module (ABM) (both used on the Series Six PLC) into a single module with significantly greater capacity and performance than that of the ASCII/BASIC module. 
  • Question:  The configuration of this module can be to function as what?  Answer:  The configuration of IC693PCM301 can be to function as the following: one or two independent CCM ports, one CCM port and one MegaBasic application using one serial port, or one MegaBasic application using one or both serial ports.
  • Question:  Dual tasking does what in the IC693PCM301?  Answer:  It allows the PCM to run a MegaBasic program and support a CCM communications channel at the same time. 
  • Question:  All of the IC693PCM301's memory is supported by what?  Answer:  It is supported by a long-life lithium battery, located on the module.
  • Question:  How many slots does the IC693PCM301 occupy?  Answer:  Each IC693PCM301 occupies a single slot in a Series 90 rack. 
  • Question:  What should I do if my IC693PCM301 is not working properly?  Answer:  Your product may need repair, which we do here at PDF Supply. 

For more information on the IC693PCM301 Programmable Coprocessor Module of the GE 90-30 Series, please see the Datasheet Manual.

 

 

Rel.

Ver.

Date

IPI

New Features

Problems Resolved

L

4.03

Aug-96

GFK-0494w

  • Disabling Time Of Day Clock Synchronization
  • Masking Serial Port Errors
  • Backplane Message Timeout
  • VTOS Time Slice Task Rotation may Stop

K

3.03

Jun-95

GFK-0494v

  • CE Mark approval

 

J

3.03

Sep-94

GFK-0494u

  • User Manual removed from shipping container

 

H

3.03

Feb-94

GFK-0494t

 

  • PLC Reference Table Access by CCM
  • CCM Target ID Check Incompatible with Previous Versions
  • CCM COMMREQ Fails with %AI or %AQ Status Word
  • CCM Slave May Begin to EOT All Incoming Headers

G

3.02

Sep-94

 

 

  • Critical Section Functions of the VTOS Operating System
  • MegaBasic SYSLINK Error with Default String Dimensions Disabled

F

3.01

Apr-93

 

  • Programmable Receiver-Enable Delay Added to CCM Protocol
  • Controlling PCM LEDs from MegaBasic
  • CCM Q/N Enquiry
  • Multidrop Enquiry

 

Common related search terms: BatteryBuyConfigurationDatasheetManualPriceRepairSpecificationTroubleshootWiring

PDF Electric & Supply Inc. sells new, new surplus and refurbished products which are sourced through independent channels. All warranties and support, if applicable, are with PDF Electric & Supply Inc. and not the manufacturer. PDF Electric & Supply Inc. is not an authorized distributor or representative for the listed manufacturers and makes no representations as to any quality control performed by any listed manufacturer on the products. The products listed on this website may vary as to their country of origin; the accessories, and other items included with the product; and the language used on the packaging, the parts, and any related instructions or printed material related to the products. This website is not sanctioned or approved by any manufacturer or tradename listed. Designated trademarks, brand names and brands appearing herein are the property of their respective owners.